Aplikasi Inverter Single Phase Off Grid di Rumah Sakit, Pabrik, Hotel, Sekolah
Bidang aplikasi:
RSUD
Pabrik
Hotel
Sekolah
Fitur Utama:
Spesifikasi teknis:
| Model | CNS115-10 | CNS115-15 | CNS115-20 | CNS115-25 | CNS115-30 | CNS115-40 | CNS115-50 | |
| INVERTER | Kekuasaan | 10kw | 15kw | 20kw | 25kw | 30kw | 40kw | 50kw |
| Penyimpanan Baterai | 100 - 200Ah | 150 - 300Ah | 200 - 400Ah | 250 - 500Ah | 300 - 600Ah | 350 - 750Ah | 450 - 900Ah | |
| Sistem PV | 10 - 12kwp | 15 - 17kwp | 20 - 25kwp | 25 - 30kwp | 30 - 35kwp | 35 - 40kwp | 45 - 50kwp | |
| Generator | 10kw | 15kw | 20kw | 25kw | 30kw | 40kw | 50kw | |
| Jaringan Listrik | 10kw / 45A | 15kw / 68A | 20kw / 90A | 25kw / 115A | 30kw / 136A | 40kw / 160A | 50kw / 227A | |
| Pengontrol Surya MPPT | 240VDC | 50A | 70A | 100A | 100A | 150A | 180A | 200A |
| TEGANGAN BATERAI | Tegangan Normal | 240 Vdc | ||||||
| Rentang Tegangan | 210 - 290 Vdc | |||||||
| Max.Arus Pengisian AC | 40A | 60A | 75A | 90A | 112A | 130A | 200A | |
| Arus baterai maksimum | 42A | 63A | 85A | 105A | 125A | 145A | 210A | |
| BIAYA AC | Pengisian Tegangan | 250 - 290 Vdc | ||||||
| Pengisian Saat Ini (Maks.) | 20Adc | 30Adc | 40Adc | 50Adc | 60Adc | 75Adc | 100Adc | |
| GARIS GRID INPUT AC | Tenaga Generator | 10kw | 15kw | 20kw | tidak ada | tidak ada | tidak ada | tidak ada |
| Tegangan | L - N: 220/230/240 Vac + / - 10% | |||||||
| GENERATOR | Tahap | 1Phase 2Wire + PE | ||||||
| Frekuensi | 50/60 Hz ± 3% | |||||||
| Fungsi start / stop | Relay kontak kering 10A (ACC hidup dan start) | |||||||
| Daya Berkelanjutan (PF = 1) | 10kw | 15kw | 20kw | 25kw | 30kw | 40kw | 50kw | |
| OUTPUT AC | Tegangan Output | L - N: 220/230/240 Vac 1Phase 2Wire + PE | ||||||
| Regulasi Tegangan | + / - 5% beban stabil. <4% beban langkah dalam 0.1 detik | |||||||
| Frekuensi | 50/60 Hz ± 0.1% | |||||||
| Distorsi Harmonik Total | THD <3% (beban linier) | |||||||
| Bentuk Gelombang | Gelombang sinus murni | |||||||
| Kemampuan Overload | > 125% beban selama 10 menit, 150% beban selama 30 detik,> 150% beban selama 10 detik, 200% beban pada 2 detik | |||||||
| ISOLASI | Tipe | Isolasi galvanik | ||||||
| EFISIENSI | Puncak Ivnerter (Maks.) | > 90% | ||||||
| PERLINDUNGAN | Sistem | Arus berlebih, Beban berlebih, Suhu berlebih, Sirkuit pendek, Voltase berlebih, voltase berlebih, voltase baterai rendah, voltase baterai berlebih | ||||||
| Tingkat IP | IP20 | |||||||
| ALARM | Alarm Operasi | Baterai lemah, Overload, Over temperature dan Fault | ||||||
| PENDINGINAN | Sistem Beroperasi | Pengatur suhu | ||||||
| LINGKUNGAN HIDUP | Tenmperature | 0 - 45 ℃ | ||||||
| Kelembaban relatif | 0 - 95% (Tanpa kondensasi) | |||||||
| PERATURAN DESAIN | Diuji Menurut | AS / NZ 3100, EN61000 - 6 - 1 / - 3, EN50178 dan IEC 62040 | ||||||
| Dimensi WxDxH (mm.) | 800 * 1030 * 1655 (dengan MPPT bawaan) | |||||||
| FISIK | Berat (kg) | 200 | 250 | 250 | 250 | 300 | 550 | 600 |
![]()